BASIC INFORMATION
Code Name
60227 IEC 01
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation
CONSTRUCTION
Conductor
Number of conductors:1
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/C according to IEC
CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
D≤25mm——————≥4D